To help enterprises improve the operational efficiency of cold storage equipment and extend the service life of units, focusing on the core points of daily inspections and periodic maintenance, the following are the key contents:
Current and voltage: current ≤ 110% of rated value, voltage fluctuation ≤ ± 10%
Equipment abnormal noise: Listen to the sound of the compressor running and check for abnormal vibration
Check the refrigerant (if the bubbles in the sight glass exceed 10%, it needs to be replenished)
Check the lubricating oil (oil level 1/2, change if it changes color)
Calibration protection switch (high voltage 1.8MPa shutdown)
Measure motor insulation (resistance>2M Ω)
Clean heat exchange equipment (air-cooled dust removal, water-cooled descaling)
Upgrade control system (update parameters, backup data)
High temperature season: Increase condenser cleaning and install air deflectors
Low temperature storage: check for evaporator defrosting and prevent icing
Record pressure and temperature data
The data shows that: Standardized maintenance can reduce the failure rate by 40% and improve energy efficiency by 12%.

Check three times a day
Pressure and temperature: Pay attention to exhaust pressure (≤ 1.8MPa) and evaporation temperatureCurrent and voltage: current ≤ 110% of rated value, voltage fluctuation ≤ ± 10%
Equipment abnormal noise: Listen to the sound of the compressor running and check for abnormal vibration
Periodic maintenance
1. Monthly
Replace the filter (if the pressure difference exceeds 0.1MPa, it must be replaced)Check the refrigerant (if the bubbles in the sight glass exceed 10%, it needs to be replenished)
Check the lubricating oil (oil level 1/2, change if it changes color)
2. Quarterly
System leak detection (soap water check pipeline interface)Calibration protection switch (high voltage 1.8MPa shutdown)
Measure motor insulation (resistance>2M Ω)
3. Annual
Compressor disassembly and inspection (seal replacement, cleaning and oil change)Clean heat exchange equipment (air-cooled dust removal, water-cooled descaling)
Upgrade control system (update parameters, backup data)
Special Scene
Long term shutdown: Preheat lubricating oil for 24 hours before restartingHigh temperature season: Increase condenser cleaning and install air deflectors
Low temperature storage: check for evaporator defrosting and prevent icing
Safety Tips
Power off operation, wear protective glovesRecord pressure and temperature data
The data shows that: Standardized maintenance can reduce the failure rate by 40% and improve energy efficiency by 12%.